BraggAngle. Bragg angle used by the MoveEnergy and MoveEnergyBrakeControl commands. It determines the energy together with the ExitOffset attribute. |
BraggOffsetInCts. Bragg offset with the unit in encoder counts (960000cts = 1 deg). It is used by the MoveEnergy command and allows the operator a fine tuning of the Bragg motor position. |
Crystal. It is used by the MoveEnergy and MoveEnergyBrakeControl commands for setting the crystal: 0 -> CrystalSi111, 1 -> CrystalSi311. |
DeltaGain. Gain value to seed the positioning error correction. The range of this value is 1 to 5. It is used by the MoveEnergyBrakeControl command. |
ExitOffset. Exit offset in mm. It is used by the MoveEnergy and MoveEnergyBrakeControl commands. It determines the energy together with the BraggAngle attribute. |
FlagFastMovement. If set to 1, the energy moves will be performed without checking if the axis are correctly set, the limits, and without setting the crystal. Useful for performing scans. |
ParOffsetInCts. Parallel offset with the unit in encoder counts (20000cts = 1 mm). It is used by the MoveEnergy command and allows the operator a fine tuning of the parallel motor position. |
PerpOffsetInCts. Perpendicular offset with the unit in encoder counts (20000cts = 1 mm). It is used by the MoveEnergy command and allows the operator a fine tuning of the perpendicular motor position. |
PhasingMode. Allows the selection of the phasing mode: 0 -> soft, 1 -> forced. It is used by the StartUp command. |
Position. Reads the energy in eV. By writting moves the monochromator to the written value (in eV). If the movement implies a change in the Bragg Angle larger than 10 degrees the movement will not be performed and the status will inform about that. |