HVisegEHS80 Class Attributes
Name
Inherited
Abstract
Attr. type
R/W type
Data type
Level
Description
ChannelStatus false false Scalar READ_WRITE Tango::DEV_DOUBLE OPERATOR Off (0), On (1), resetEmergencyOff (2), setEmergencyOff (3), clearEvents (10)\n\nRead: An enumerated value which shows the current state of\n the output channel.\n Write: Change the state of the channel.\n If the channel is On, and the write value is Off, then the channel\n will switch Off.\n If the channel is Off, and the write value is On, and if no other\n signals (mainInhibit, outputInhibit, outputEmergencyOff or outputFailureMaxCurrent)\n are active, then the channel will switch on.\n \n If the write value is resetEmergencyOff, then the channel will \n leave the state EmergencyOff. A write of clearEvents is necessary\n before the voltage can ramp up again.\n If the write value is setEmergencyOff, then the channel will have \n the state EmergencyOff, which means that the High Voltage will \n switch off without a ramp and reset of the outputVoltage to null volt.\n \n If the write value is clearEvents, then all failure messages \n of the outputStatus will be reset (all channel events, all module events\n and the state emergencyOff).
MeasTerminalVoltage false false Scalar READ Tango::DEV_DOUBLE OPERATOR The measured voltage at the output terminals.
MeasSenseVoltage false false Scalar READ Tango::DEV_DOUBLE OPERATOR The measured voltage at the sense input lines.
SetCurrent false false Scalar READ_WRITE Tango::DEV_DOUBLE OPERATOR The current limit of the channel.
MeasCurrent false false Scalar READ Tango::DEV_DOUBLE OPERATOR The measured output current.
RampSpeed false false Scalar READ_WRITE Tango::DEV_DOUBLE OPERATOR Voltage Ramp Speed in %
It is changed for the whole module.
Needs a kill-disable to allow for changes> 1%
snmpset -v 2c -m +WIENER-CRATE-MIB -c guru 192.168.132.153 groupsSwitch.64 i 4
ChannelStatusStr false false Scalar READ Tango::DEV_STRING OPERATOR
SetVoltage false false Scalar READ_WRITE Tango::DEV_DOUBLE OPERATOR The nominal output voltage of the channel.
CrateSlot false false Scalar READ Tango::DEV_LONG OPERATOR Crate Slot (from 1 to 5)
ChannelNumber false false Scalar READ Tango::DEV_LONG OPERATOR Channel Number (from 1 to 16)
Resistance false false Scalar READ Tango::DEV_DOUBLE OPERATOR MeasSenseVoltage/MeasCurrent
OutputStatus false false Scalar READ Tango::DEV_DOUBLE OPERATOR





There is no dynamic attribute defined.