PhyMotionMotor Class Attributes
Name
Inherited
Abstract
Attr. type
R/W type
Data type
Level
Description
MovementType false false Scalar READ_WRITE Tango::DEV_LONG OPERATOR Type of movement (free, relatib/absolute, reference move):
0 -> rotational
1 -> hardware limit switches
2 -> software limit switches
3 -> hw and sw limit switches
BaseRate false false Scalar READ_WRITE Tango::DEV_LONG OPERATOR The motor starts to move with this rate, then accelerates
SlewRate false false Scalar READ_WRITE Tango::DEV_LONG OPERATOR The motor speed
Acceleration false false Scalar READ_WRITE Tango::DEV_LONG OPERATOR The acceleration
UnitLimitMin false false Scalar READ_WRITE Tango::DEV_DOUBLE OPERATOR
UnitLimitMax false false Scalar READ_WRITE Tango::DEV_DOUBLE OPERATOR
UnitBacklash false false Scalar READ_WRITE Tango::DEV_DOUBLE OPERATOR
Position false false Scalar READ_WRITE Tango::DEV_DOUBLE OPERATOR
UnitCalibration false false Scalar READ_WRITE Tango::DEV_DOUBLE OPERATOR Position = (Hw position) + UnitCalibration
LimitSwitchType false false Scalar READ_WRITE Tango::DEV_LONG OPERATOR 0 -> opener pos, neg, mit and ref limits
7 -> closer pos, neg, mit and ref limits
StopCurrent false false Scalar READ_WRITE Tango::DEV_DOUBLE OPERATOR
RunCurrent false false Scalar READ_WRITE Tango::DEV_DOUBLE OPERATOR
Temperature false false Scalar READ Tango::DEV_DOUBLE OPERATOR Current power stage temperature.
Conversion false false Scalar READ_WRITE Tango::DEV_DOUBLE OPERATOR The conversion factor, steps = conversion*units
Monitoring false false Scalar READ_WRITE Tango::DEV_LONG EXPERT If 1 monitoring is activated. Monitoring axis that are not active causes problems in
the movement of the other axe.
MotorTemperature false false Scalar READ Tango::DEV_DOUBLE OPERATOR Current motor temperature.
MotorTempWarning false false Scalar READ_WRITE Tango::DEV_DOUBLE OPERATOR Motor temperature warning.
MotorTempShutOff false false Scalar READ_WRITE Tango::DEV_DOUBLE OPERATOR Motor temperature shut-off
EmergencyStopFreq false false Scalar READ_WRITE Tango::DEV_LONG OPERATOR Emergency stop ramp
AutomaticActivation false false Scalar READ_WRITE Tango::DEV_LONG OPERATOR 0 = Power stage is deactivated after power on
1 = Power stage is activated after power on
LimitSwitch false false Scalar READ Tango::DEV_DOUBLE OPERATOR 1 if motor in limit switch
PreferentialDirection false false Scalar READ_WRITE Tango::DEV_LONG OPERATOR
StepResolution false false Scalar READ_WRITE Tango::DEV_LONG OPERATOR 0 = 1/1 step
1 = 1/2 step
2 = 1/2.5 step
3 = 1/4 step
4 = 1/5 step
5 = 1/8 step
6 = 1/10 step
7 = 1/16 step
8 = 1/20 step
9 = 1/32 step
10 = 1/64 step
11 = 1/128 step
12 = 1/256 step
13 = 1/512 step
ICStatus false false Scalar READ Tango::DEV_STRING OPERATOR Limit switch center status
IPlusStatus false false Scalar READ Tango::DEV_STRING OPERATOR Limit switch + status
IMinusStatus false false Scalar READ Tango::DEV_STRING OPERATOR Limit switch - status
ISPlusStatus false false Scalar READ Tango::DEV_STRING OPERATOR Software limit switch + status
ISMinusStatus false false Scalar READ Tango::DEV_STRING OPERATOR Software limit switch - status
SaveToFLASHMem false false Scalar READ_WRITE Tango::DEV_LONG OPERATOR If 1 current settings will be written to FLASH Memory after writting any attribute.





There is no dynamic attribute defined.