PlcUndulator Class Attributes
Name
Inherited
Abstract
Attr. type
R/W type
Data type
Level
Description
CurrentGap false false Scalar READ Tango::DEV_LONG OPERATOR The current Gap in um.
DesiredGap false false Scalar READ_WRITE Tango::DEV_LONG OPERATOR The desired Gap in um.
MaxGap false false Scalar READ Tango::DEV_LONG OPERATOR The Max allowed value for the Gap, in um.\nIt is at most 225000 um.
MinGap false false Scalar READ Tango::DEV_LONG OPERATOR The Min allowed value for the Gap, in um.\nIt is at least 8000 um.
CurrentTaper false false Scalar READ Tango::DEV_LONG OPERATOR The current Taper in um.
DesiredTaper false false Scalar READ_WRITE Tango::DEV_LONG OPERATOR The desired Taper in um.
CurrentSpeed false false Scalar READ Tango::DEV_LONG OPERATOR The current Speed.\n1 unit corresponds to 0.00856 um/s.
DesiredSpeed false false Scalar READ_WRITE Tango::DEV_LONG OPERATOR The desired Speed.\n1 unit corresponds to 0.00856 um/s.
StatusByte false false Scalar READ Tango::DEV_USHORT OPERATOR Undulator Status Byte.
CtrlByte false false Scalar READ Tango::DEV_USHORT OPERATOR External Control Byte.
CurrentUnitPosition false false Scalar READ Tango::DEV_DOUBLE EXPERT Unused.
UnitLimitMax false false Scalar READ_WRITE Tango::DEV_DOUBLE EXPERT Unused.
UnitLimitMin false false Scalar READ_WRITE Tango::DEV_DOUBLE EXPERT Unused.
CwLimit false false Scalar READ Tango::DEV_LONG EXPERT Unused.
CcwLimit false false Scalar READ Tango::DEV_LONG EXPERT Unused.
SettleTime false false Scalar READ_WRITE Tango::DEV_DOUBLE EXPERT Unused.
FlagProtected false false Scalar READ_WRITE Tango::DEV_LONG EXPERT Unused.
CurrentShift false false Scalar READ Tango::DEV_LONG OPERATOR The current Shift in um (only valid for pu04 and pu23, 0 in other cases)
DesiredShift false false Scalar READ_WRITE Tango::DEV_LONG OPERATOR The desired Shift in um (only valid for pu04 and pu23, 0 in other cases).
CurrentShiftMode false false Scalar READ Tango::DEV_LONG OPERATOR The current shift mode (only valid for pu04 and pu23, 0 in other cases)
DesiredShiftMode false false Scalar READ_WRITE Tango::DEV_LONG OPERATOR Desired shift mode (only valid for pu04 and pu23, 0 in other cases)
RecentWrites false false Spectrum READ Tango::DEV_STRING OPERATOR Contains the recent output operations





There is no dynamic attribute defined.