|  AxisName. Read/Write user defined name for the axis. | 
|  Channel_rd. Read power stage channel number (as given in the property channel). | 
|  Deactivation. Read/Write deactivation. 0 = activated, 1 = deactivated. | 
|  DeactivationStr. Read Deactivation and show the value as a meanfull string. | 
|  DelayTime. Read/Write delay time. Read value in ms. Valid write values: from 0 to 15. set_value=real_value(ms) O=1, 1=2, 2=4, 3=6, 4=8, 5=10, 6=12, 7=14, 8=16, 9=20, 10=40, 11=60, 12=100, 13=200, 14=500, 15=1000. | 
|  DelayTimeInfo. String for writing any info about the delay time. | 
|  Error. Inquiry error from the power stage and return the corresponding description. | 
|  ErrorZMXConnection. List of commands send to the ZMX and date when an connection error was produced. It is reset by executing the command ResetErrorZMXConnection or after 5 errors are produced. It uses the Checksum for detecting errors in writing or reading. | 
|  FlagChangeNotSaved. If 1, some setting of the power stage has been changed (by writting to the corresponding attribute) and not write to EPROM was performed after that. Only read value. | 
|  FlagErrorZMXConnection. It is 1 if an error was produced by reading/wrinting from/to the ZMS. It is reset to 0 by executing the command ResetErrorZMXConnection. It uses the Checksum for detecting errors in writing or reading. | 
|  FlagSaveAutomatically. If set to 1 an automatic write to EPROM will be performed after some setting is changed (by writting to the corresponding attribute). | 
|  FlagThreadRunning. 1 if the thread is running, in that case not read or write operation will be performed. Only read. | 
|  HwDeactivation. 1 if hardware is not active. Only read. | 
|  InputLogicLevel. Read/Write logic level of all inputs. 0 = high, 1 = low. | 
|  InputLogicLevelStr. Read InputLogicLevel and show the value as a meanfull string. | 
|  IntermediateVoltage. Read intermediate voltage (in V). | 
|  IntermediateVoltageInfo. String for writing any info about the intermediate voltage. | 
|  OperationMode. Status Service Bus. 0 = off, 1 = on. The Service Bus status is activated in ZMX+ power stage by the 'SB active' DIP switch. By software one can only read the status. | 
|  OperationModeStr. Read OperationMode and show the value as a meanfull string. | 
|  Overdrive. Read/Write overdrive. 0 = on, 1 = off. | 
|  OverdriveStr. Read Overdrive and show the value as a meanfull string. | 
|  PathOutputFiles. Path where the commands SaveToOutputFile, LoadFromOutputFile, ReadFileContent and ReadFilesInOutputPath are performed. | 
|  PowerStageStatus. Read the current status of the power stage and return the corresponding description. | 
|  PreferentialDirection. Read/Write preferential direction. 1=preferential direction, 0=contrary to preferential direction. | 
|  PreferentialDirectionStr. Read PreferentialDirection and show the value as a meanfull string. | 
|  RunCurrent. Read/Write the run current (in A). | 
|  StepWidth. Read/Write step width. Valid values: 0 to 13. 0=1/1, 2=1/2, 3=1/4, 4=1/5, 5=1/8, 6=1/10, 7=1/16, 8=1/20, 9=1/32, 10=1/64, 11=1/128, 12=1/256, 13=512. | 
|  StepWidthStr. Read real value of step width in string format. | 
|  StopCurrent. Read/Write the stop current (in A). | 
|  Temperature. Read current temperature from the power stage (in degrees). | 
|  VersionFPGA. Show version of the FPGA. | 
|  VersionPS. Show version of the Power Stage.
 
  |